Model Number |
HYR 2-815 |
| * |
Application |
|
- HYR 2-815 Series Regulator is designed for to use commercial place such as restaurant business, hotel, school, public building or factory etc to supply natural gas.
- It is suit for boiler or burning equipment device, small & medium device regulator.
|
|
|
|
| * |
Character |
|
- It is easy to install (verticality and horizontality connecting pipe, Case rotate attachment)
- Can choice proper orifice according to first stage pressure and capacity.
- Orifice, Seat disc etc replacement and maintain is possible without disconnecting regulator body to pipe.
|
|
|
|
|
| * |
Specifications |
|
|
Inlet Pressure range |
0.015~0.99 MPa |
|
Outlet Pressure range |
1.6~45.0kPa(160~4500mmH2O) |
|
Relief valve Setting Pressure |
3.2~67.0kPa(320~6700mmH2O) |
|
OPSO Setting Pressure |
3.0~70.0kPa(300~7000mmH2O) |
|
Max. capacity |
Refer to detailed specification |
|
Connection Size |
50A-10K flange(Rf type) |
|
Model |
Type |
|
HYR 2-815 |
built-in relief valve, OPSO |
|
HYR 2-815 OPSO |
With OPSO | |
| * |
Capacity Table |
|
HYR 2-815 Series Capacity table is indicating inlet pressure changing and capacity fluctuation according to orifice size. Standard object is natural gas. (gravity=0.6, standard state N ㎥/hr) |
|

|
|
|
| * |
HYR 2-815 OPSO Regulator Construction |
|
|
|
|
| * |
SPRING |
|
|
Adjusting Spring |
|
Spring No. |
Pressure Range |
Color |
|
Ms 2815 |
1.6~2.6kPa |
Green |
|
Ms 2815-15 |
10~18kPa |
White |
|
Ms 2815-25 |
16~30kPa |
Biue |
|
Ms 2815-40 |
28~45kPa |
Yello |
| OPSO Spring |
| Spring No. |
Pressure Range |
Color |
| Os 81 |
3.0~4.8kPa |
Green |
| Os 81-15 |
20~27kPa |
White |
| Os 81-25 |
33~45kPa |
Biue |
| Os 81-40 |
52~70kPa |
Yello |
| Relief valve Spring |
| Spring No. |
Pressure Range |
Color |
| Rs 215 |
P2+1.2~2.8kPa |
Green |
| Rs 215-15 |
P2+4.0~9.0kPa |
White |
| Rs 215-25 |
P2+10.0~15.0kPa |
Biue |
| Rs 215-40 |
P2+12.0~27.0kPa |
Yello |
Unit : mmH20
|
| * |
Regulator abnormality cause and settlement |
|
| 1) Outlet part second pressure is drop |
|
1) Cause |
|
|
- Orifice size is small against to using capacity
- Gas supply is interrupted due to block gas filter
- Diaphragm is expanded due to long time using
- OPSO is locked up
| |
|
2) Settlement |
|
|
- Replace suitable orifice according to using capacity
- Disassembly gas filter and cleaning inside
- Disassembly case and replace diaphragm
- Block inlet & outlet valve and release gas. And then, restore OPSO.
| |
|
|
| 2) Outlet part second pressure is increasing |
|
1) Cause |
|
|
- Lock-up condition is bad due to valve seat or orifice wear, crack etc
- First stage inlet pressure is applied toward OPSO because of OPSO Shaft O-ring damage
- Assembly lever linked diaphragm operation is not good
- Volume changing is happen due to temperature
- First stage inlet pressure is applied due to orifice sealing condition
| |
|
2) Settlement |
|
|
- Disconnecting case from pipe and replace valve seat and orifice
- Disconnecting OPSO from pipe and replace shaft O-ring
- Disassembly case and replace Assembly lever
- Keeping warm the expose pipe
- Re-assembly orifice sealing by sealing materials
| |
|
|
| 3) In case of regulator hunting |
|
1) Cause |
|
|
- Orifice size is too much big against to capacity and pressure
- First stage pressure is unstabilized
- Inflow contamination materials or humidity to inside of second stage pipe
- Happening spring and diaphragm deformation due to long time use
- Large volume of gas is instantaneously & repeatedly flow and cut off.
| |
|
2) Settlement |
|
|
- Replace suitable orifice according to using capacity and pressure
- Disassembly and inspect filter
- Remove inside of contamination materials and humidity
- Disassembly case and inspect and then replace spring and diaphragm
- Secure sufficient second stage pipe volume
| | | |
|
|
|
|
| |
|
|
|