 Model Number HYR 2-815

* Application
  1. HYR 2-815 Series Regulator is designed for to use commercial place such as restaurant business, hotel, school, public building or factory etc to supply natural gas.
  2. It is suit for boiler or burning equipment device, small & medium device regulator.
* Character
  1. It is easy to install (verticality and horizontality connecting pipe, Case rotate attachment)
  2. Can choice proper orifice according to first stage pressure and capacity.
  3. Orifice, Seat disc etc replacement and maintain is possible without disconnecting regulator body to pipe.
* Specifications
Inlet Pressure range
0.015~0.99 MPa
Outlet Pressure range
1.6~45.0kPa(160~4500mmH2O)
Relief valve Setting Pressure
3.2~67.0kPa(320~6700mmH2O)
OPSO Setting Pressure
3.0~70.0kPa(300~7000mmH2O)
Max. capacity
Refer to detailed specification
Connection Size
50A-10K flange(Rf type)

Model
Type
HYR 2-815
built-in relief valve, OPSO
HYR 2-815 OPSO
With OPSO

* Capacity Table
HYR 2-815 Series Capacity table is indicating inlet pressure changing and capacity fluctuation according to orifice size. Standard object is natural gas.
(gravity=0.6, standard state N ㎥/hr)

* HYR 2-815 OPSO Regulator Construction

* SPRING
Adjusting Spring
Spring No.
Pressure Range
Color
Ms 2815
1.6~2.6kPa
Green
Ms 2815-15
10~18kPa
White
Ms 2815-25
16~30kPa
Biue
Ms 2815-40
28~45kPa
Yello

OPSO Spring
Spring No. Pressure Range Color
Os 81 3.0~4.8kPa Green
Os 81-15 20~27kPa White
Os 81-25 33~45kPa Biue
Os 81-40 52~70kPa Yello

Relief valve Spring
Spring No. Pressure Range Color
Rs 215 P2+1.2~2.8kPa Green
Rs 215-15 P2+4.0~9.0kPa White
Rs 215-25 P2+10.0~15.0kPa Biue
Rs 215-40 P2+12.0~27.0kPa Yello
Unit : mmH20
* Regulator abnormality cause and settlement
1) Outlet part second pressure is drop
1) Cause
  1. Orifice size is small against to using capacity
  2. Gas supply is interrupted due to block gas filter
  3. Diaphragm is expanded due to long time using
  4. OPSO is locked up
2) Settlement
  1. Replace suitable orifice according to using capacity
  2. Disassembly gas filter and cleaning inside
  3. Disassembly case and replace diaphragm
  4. Block inlet & outlet valve and release gas. And then, restore OPSO.
2) Outlet part second pressure is increasing
1) Cause
  1. Lock-up condition is bad due to valve seat or orifice wear, crack etc
  2. First stage inlet pressure is applied toward OPSO because of OPSO Shaft O-ring damage
  3. Assembly lever linked diaphragm operation is not good
  4. Volume changing is happen due to temperature
  5. First stage inlet pressure is applied due to orifice sealing condition
2) Settlement
  1. Disconnecting case from pipe and replace valve seat and orifice
  2. Disconnecting OPSO from pipe and replace shaft O-ring
  3. Disassembly case and replace Assembly lever
  4. Keeping warm the expose pipe
  5. Re-assembly orifice sealing by sealing materials
3) In case of regulator hunting
1) Cause
  1. Orifice size is too much big against to capacity and pressure
  2. First stage pressure is unstabilized
  3. Inflow contamination materials or humidity to inside of second stage pipe
  4. Happening spring and diaphragm deformation due to long time use
  5. Large volume of gas is instantaneously & repeatedly flow and cut off.
2) Settlement
  1. Replace suitable orifice according to using capacity and pressure
  2. Disassembly and inspect filter
  3. Remove inside of contamination materials and humidity
  4. Disassembly case and inspect and then replace spring and diaphragm
  5. Secure sufficient second stage pipe volume